The All-Round Talent. Smart, secure plant control. Higher output and profitability despite compact design.
| Engine type | Unit | TCG 3020 V12 P = Optimized for high electrical efficiency 50 Hz |
TCG 3020 V12 R = Optimized for high total efficiency 50 Hz |
TCG 3020 V16 P = Optimized for high electrical efficiency 50 Hz |
TCG 3020 V16 R = Optimized for high total efficiency 50 Hz |
TCG 3020 V20 P = High electrical efficiency 50 Hz |
TCG 3020 V20 P = High electrical efficiency 60 Hz |
TCG 3020 V20 R = High total efficiency 50 Hz |
TCG 3020 V20 R = High total efficiency 60 Hz |
TCG 3020 V20 FQ = High efficiency for requested power 50 Hz |
TCG 3020 V20 FQ = High efficiency for requested power 60 Hz |
TCG 3020 V20 RV = High response for requested power 50 Hz |
TCG 3020 V20 RV = High response for requested power 60 Hz |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Electrical output | kW | 1,380 | 1,380 | 1,840 | 1,840 | 2,300 | 2,300 | 2,300 | 2,300 | 2,000 | 2,000 | 2,000 | 2,000 |
| Electrical efficiency** | % | 45 | 44 | 44.7 | 44 | 45 | 44.4 | 44 | 43.7 | 44.4 | 43.9 | 43.7 | 43.4 |
| Thermal output | kW | 1,949 | 1,982 | 2,026 | 2,038 | ||||||||
| Thermal efficiency** | % | 42.3 | 43.6 | 42.6 | 43.6 | 42.3 | 42.5 | 43.6 | 43.6 | 43.3 | 43.5 | 42.9 | 44.2 |
| Overall efficiency | % | 87.3 | 87.6 | 87.3 | 87.6 | 87.3 | 86.9 | 87.6 | 87.3 | 87.7 | 87.4 | 87.2 | 87.6 |
| Power to heat ratio*** | – | 1.06 | 1.01 | 1.05 | 1.01 | 1.06 | 1.04 | 1.01 | 1.01 | 1.02 | 1.01 | 0.99 | 0.98 |
* With 5% O2 and dry exhaust gas
** According to ISO 3046-1
*** The power to heat ratio is calculated by dividing the electrical efficiency by the thermal efficiency. Please remember that this is a theoretical value that may deviate from actually measured values.
The values given in these tables are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.
| Engine type | Unit | TCG 3020 V12 P = High electrical efficiency 50 Hz |
TCG 3020 V12 R = High total efficiency 50 Hz |
TCG 3020 V16 P = High electrical efficiency 50 Hz |
TCG 3020 V16 R = High total efficiency 50 Hz |
TCG 3020 V20 P = High electrical efficiency 50 Hz |
TCG 3020 V20 P = High electrical efficiency 60 Hz |
TCG 3020 V20 R = High total efficiency 50 Hz |
TCG 3020 V20 R = High total efficiency 60 Hz |
TCG 3020 V20 FQ = High efficiency for requested power 50 Hz |
TCG 3020 V20 FQ = High efficiency for requested power 60 Hz |
TCG 3020 V20 RV = High response for requested power 50 Hz |
TCG 3020 V20 RV = High response for requested power 60 Hz |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Electrical output | kW | 1,380 | 1,380 | 1,840 | 1,840 | 2,300 | 2,300 | 2,300 | 2,300 | 2,000 | 2,000 | 2,000 | 2,000 |
| Electrical efficiency** | % | 43.9 | 43.9 | 44 | 42.9 | 44 | 43.5 | 42.9 | 42.6 | 43.4 | 42.9 | 42.3 | 42.3 |
| Thermal output | kW | 2,031 | 2,065 | 2,123 | 2,136 | ||||||||
| Thermal efficiency** | % | 43.2 | 44.5 | 43.5 | 44.5 | 43.1 | 43.3 | 44.6 | 44.6 | 44.1 | 44.3 | 45.2 | 45.2 |
| Overall efficiency | % | 87 | 87 | 87 | 87 | 87 | 88 | 87 | 87 | 88 | 88 | 88 | 88 |
| Power to heat ratio*** | – | 1.02 | 0.98 | 1 | 0.96 | 1.02 | 1 | 0.96 | 0.96 | 0.98 | 0.97 | 0.94 | 0.94 |
* With 5% O2 and dry exhaust gas
** According to ISO 3046-1
*** The power to heat ratio is calculated by dividing the electrical efficiency by the thermal efficiency. Please remember that this is a theoretical value that may deviate from actually measured values.
The values given in these tables are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.
| Engine type | Unit | TCG 3020 V12 P-H: High Efficiency + 25H2-Kit 50 Hz |
TCG 3020 V12 R-H: High Response + 25H2-Kit 50 Hz |
TCG 3020 V16 P-H: High Efficiency + 25H2-Kit 50 Hz |
TCG 3020 V16 R-H: High Response + 25H2-Kit 50 Hz |
TCG 3020 V20 P-H: High Efficiency + 25H2-Kit 50 Hz |
TCG 3020 V20 P-H: High Efficiency + 25H2-Kit 60 Hz |
TCG 3020 V20 R-H: High Response + 25H2-Kit 50 Hz |
TCG 3020 V20 R-H: High Response + 25H2-Kit 60 Hz |
TCG 3020 V20 FQ-H: High Efficiency + 25H2-Kit 50 Hz |
TCG 3020 V20 FQ-H: High Efficiency + 25H2-Kit 60 Hz |
TCG 3020 V20 RV-H: High Response + 25H2-Kit 50 Hz |
TCG 3020 V20 RV-H: High Response + 25H2-Kit 60 Hz |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Electrical power** | kW | 1,380 | 1,380 | 1,840 | 1,840 | 2,300 | 2,300 | 2,000 | 2,000 | ||||
| Electrical efficiency | % | 46 | 43.9 | 44.6 | 43.6 | 44.6 | 43.6 | 44 | 43.3 | ||||
| Thermal efficiency (at 8%) | % | 42.5 | 43.9 | 42.6 | 43.9 | 42.6 | 43.9 | 43.6 | 44.6 | ||||
| Total efficiency | % | 87.1 | 87.5 | 87.2 | 87.5 | 87.2 | 87.5 | 87.6 | 87.9 | ||||
| Power to heat ratio *** | – | 1.05 | 1 | 1.05 | 0.99 | 1.05 | 0.99 | 1.01 | 0.97 |
* for 5 % O2 and dry exhaust gas
** according to ISO 3046-1
*** The power to heat ratio is calculated by dividing the electrical efficiency by the thermal efficiency. Please remember that this is a theoretical value that may deviate from actually measured values.
The values given in this table are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.
| Engine type | TCG 3020 V20 Z = Optimized for operation with propane gas 50 Hz |
TCG 3020 V20 Z = Optimized for operation with propane gas 60 Hz |
|---|---|---|
| Electrical output | 1,880* | 1,880* |
| Electrical efficiency** | 41 | 41.5 |
| Thermal output | 2,063 | 2,078 |
| Thermal efficiency** | 45.9 | 45.8 |
| Overall efficiency | 87.7 | 87.3 |
| Power to heat ratio*** | 0.91 | 0.91 |
* This electrical output of 1880 kWel is also achieved with natural gas applications.
** According to ISO 3046-1
*** The power to heat ratio is calculated by dividing the electrical efficiency by the thermal efficiency. Please remember that this is a theoretical value that may deviate from actually measured values.
The values given in these tables are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.
| Engine type | TCG 3020 V12 50Hz |
TCG 3020 V16 50Hz |
TCG 3020 V20 50 Hz |
TCG 3020 V20 60 Hz |
TCG 3020 V20 Z = Optimized for operation with propane gas 50 Hz |
TCG 3020 V20 Z = Optimized for operation with propane gas 60 Hz |
|---|---|---|---|---|---|---|
| Bore / stroke | 170/195 mm | 170/195 mm | 170/195 mm | 170/195 mm | 170/195 mm | 170/195 mm |
| Displacement | 53 dm3 | 71 dm3 | 89 dm3 | 89 dm3 | 89 dm3 | 89 dm3 |
| Speed | 1,500 min-1 | 1,500 min-1 | 1,500 min-1 | 1,500 min-1 | 1,500 min-1 | 1,500 min-1 |
| Mean piston speed | 9.8 m/s | 9.8 m/s | 9.8 m/s | 9.8 m/s | 9.8 m/s | 9.8 m/s |
| Length | 5,080 mm | 6,100 mm | 6,600 mm | 7,738 mm | 6,600 mm | 7,738 mm |
| Width | 1,815 mm | 1,815 mm | 1,815 mm | 1,815 mm | 1,815 mm | 1,815 mm |
| Height | 2,190 mm | 2,190 mm | 2,190 mm | 2,551 mm | 2,190 mm | 2,551 mm |
| Dry weight gen-set | 12,000 kg | 17,400 kg | 21,400 kg | 21,200 kg | 17,980 kg | 21,200 kg |
The values given in this table are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.
| Engine type | TCG 3020 V12 X = Optimized for operation with all biogases 50 Hz |
TCG 3020 V16 X = Optimized for operation with all biogases 50 Hz |
TCG 3020 V20 X = Optimized for operation with all biogases 50 Hz |
TCG 3020 V20 X = Optimized for operation with all biogases 60 Hz |
TCG 3020 V20 X = Optimized for operation with all biogases for requested power 50 Hz |
TCG 3020 V20 X = Optimized for operation with all biogases for requested power 60 Hz |
|---|---|---|---|---|---|---|
| Electrical output | 1,380 kW | 1,840 kW | 2,300 kW | 2,300 kW | 2,000 kW | 2,000 kW |
| Electrical efficiency** | 43.6 % | 43.6 % | 43.6 % | 43.1 % | 42.2 % | 42.7 % |
| Thermal output | 2,254 kW | 2,206 kW | 2,015 kW | 1,983 kW | ||
| Thermal efficiency** | 42.7 % | 42.7 % | 42.9 % | 41.4 % | 43.5 % | 42.3 % |
| Overall efficiency | 86 % | 86 % | 87 % | 85 % | 87 % | 85 % |
| Power to heat ratio*** | 1.02 | 1.02 | 1.02 | 1.07 | 1.04 | 1.03 |
* With 5% O2 and dry exhaust gas
** According to ISO 3046-1
*** The power to heat ratio is calculated by dividing the electrical efficiency by the thermal efficiency. Please remember that this is a theoretical value that may deviate from actually measured values.
The values given in these tables are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.
| Engine type | TCG 3020 V12 X = Optimized for operation with all biogases 50 Hz |
TCG 3020 V16 X = Optimized for operation with all biogases 50 Hz |
TCG 3020 V20 X = Optimized for operation with all biogases 50 Hz |
TCG 3020 V20 X = Optimized for operation with all biogases 60 Hz |
TCG 3020 V20 X = Optimized for operation with all biogases for requested power 50 Hz |
TCG 3020 V20 X = Optimized for operation with all biogases for requested power 60 Hz |
|---|---|---|---|---|---|---|
| Electrical output | 1,380 kW | 1,840 kW | 2,300 kW | 2,300 kW | 2,000 kW | 2,000 kW |
| Electrical efficiency** | 42.6 % | 42.6 % | 42.7 % | 42.2 % | 42.2 % | 41.7 % |
| Thermal output | 2,346 kW | 2,293 kW | 2,097 kW | 2,060 kW | ||
| Thermal efficiency** | 43.4 % | 43.5 % | 43.6 % | 42 % | 44.3 % | 43 % |
| Overall efficiency | 86 % | 86 % | 86.3 % | 84 % | 87 % | 85 % |
| Power to heat ratio*** | 0.98 | 0.98 | 1 | 1 | 0.97 | 0.97 |
* With 5% O2 and dry exhaust gas
** According to ISO 3046-1
*** The power to heat ratio is calculated by dividing the electrical efficiency by the thermal efficiency. Please remember that this is a theoretical value that may deviate from actually measured values.
The values given in these tables are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.
| First Service * | Cylinder head inspection | General overhaul | |
|---|---|---|---|
| High gas quality (natural gas, mega gas (purified) propane gas) |
4,000 oh | 40,000 oh** | 80,000 oh |
| Medium gas quality (biogas (purified), mine gas) |
4,000 oh | 32,000 oh** | 64,000 oh |
| Gas quality Low (biogas, landfill gas, sewage gas) |
3,000 oh | 24,000 oh** | 48,000 oh |
* at first commissioning [E10]
** at the latest
The values given in this table are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.